Ten common dry type transformer temperature controllers show troubleshooting methods

/
/

1. Dry transformer temperature controller has no display

Fault causes: ① The thermostat power supply is not connected; ② Fuse is blown.

Treatment methods: (1) switch on the power supply; ② Replace the fuse.

2, dry type transformer temperature controller shows a phase or three-phase flashing and shows "-op -"

Fault causes: (1) The corresponding input signal is greater than the measurement range of dry transformer temperature controller; ②Pt100 temperature sensor measurement loop has large contact resistance.

Treatment methods: ① Use Pt100 temperature sensor with temperature controller; ② Eliminate the contact resistance of the line.

3, dry type transformer temperature controller shows a phase or three-phase flashing and shows "-Oh -"

Fault causes: (1) the corresponding input signal is greater than the temperature controller measurement range; ② The sensor measurement loop has a large contact resistance.

Treatment methods: ① Use Pt100 temperature sensor with temperature controller; ② Eliminate the contact resistance of the line.

4. Dry type transformer temperature controller displays a phase or three phases flashing and displays "-ol -"

Fault causes: (1) The corresponding input signal is less than the temperature controller measurement range; ② There is a short circuit in the measuring circuit of the temperature sensor.

Treatment methods: ① Use Pt100 temperature sensor with temperature controller; ② Check the measurement line of the sensor.

5. Dry type transformer temperature controller flashes "-er -"

Fault causes: (1) Sensor measurement loop wiring error; ② The temperature controller is faulty.

Treatment methods: (1) Check the external connection of the temperature controller; ② Contact Changhui Instrument Manufacturing Co., LTD.

6, fixed display of a phase temperature

Fault cause: dry type transformer temperature controller in large value display state.

Solution: Press the large/circuit key to return the thermostat to the circuit display state.

7, the three-phase temperature is lower than 80oC, but the fan is still running

Fault causes: (1) The fan starting set value or return value is changed; ② The fan is started manually.

Treatment methods: (1) readjust the set value; ② Press the auto/Manual button to make the fan under automatic control.

8, from the dry transformer temperature controller display, three-phase temperature imbalance

Fault reasons: ①Pt100 platinum resistance is not fixed into the temperature hole; ② The three-phase temperature of the transformer is different.

Treatment methods: ① re-fixed platinum resistance; ② Normal phenomenon.

9. The temperature of the fan is not reached, but the fan runs automatically

Fault causes: ① The fan is started manually; ② The system fan starts and stops at a scheduled time.

Treatment methods: ① press the ▲ key to close the fan; ② It is a normal phenomenon.

10. After manually starting the fan on the dry transformer temperature controller, the fan cannot be manually shut down

Fault cause: The measured temperature is right between the temperature of automatic starting and stopping of the fan.

Treatment method: It is a normal phenomenon.